Utility Load Control
Bottom 2-screw terminal block marked blue and blu/wht. Remove the jumper and extend the two wires to the
utility furnished control device. For electric energy operation (off-peak) the two blue wires represent contact
closure as shipped. Do not apply external voltage or external power to the blue wires, they are simply
looking for a closed contact during off-peak.
The maximum “AC noise” on the blue wire is 5 volts, peak to peak. The blue/white wire is actually
common and if grounding is proper as suggested in the next paragraph, this should dampen any effect. But
it is always good practice to run these wires separate from any current carrying line voltage Romex or other
conductors.
One load control wire pair handles both winter and summer interrupt.
If load control reverse logic is required, a “closed to interrupt contact” can be connected to SB SW to
COM. Another way to resolve this issue is through the use of an interposing relay. Consult factory if an
interposing relay is required.
If load management interrupt does not apply, simply leave the blue wires jumpered.
Grounding
The 24-volt transformer and EZGEO board common are grounded at the compressor contactor coil common
side.