AUX EL Series Instructions d'exploitation Page 38

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 56
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 37
09/11/2014 36 NI401
Troubleshooting/Repair Helps
1. This EZGEO controller contains several interference suppression components, but as an electronic logic
product, unpredictable and unusual transients or interferences may sometimes cause strange results. If the
EZGEO controller is “acting strange”, one immediate step would be power down reset. Simply turn off the 24-
volt source power (probably furnace or air handler circuit breaker), when the green LED goes out, count to 10,
and re-energize power supply.
2. The terminal blocks for control wire hook-up are designed for a wire insertion and screw clamp down. If there is
no wire connected and the screw is loose, the screw may not necessarily make a good electrical contact to the
inside components. Example – if you are jumpering the thermostat terminals without thermostat wire connection
or if you are attempting to measure voltage on the screw head, you may get erroneous or unpredictable results if
the screw is not tightened down.
3. Use general heating system logic information and basic understanding of the terminal block wiring functions
when measuring voltage to determine proper operation of this module.
4. The outdoor sensor must be located outdoors for this controller to correctly operate. Do not leave the outdoor
sensor “hanging in conditioned space” and attempt to run this system. Note: OT sensor tip must be up.
Vue de la page 37
1 2 ... 33 34 35 36 37 38 39 40 41 42 43 ... 55 56

Commentaires sur ces manuels

Pas de commentaire